IFS7002-4
 Click to Zoom
Interactive Fire Control Panel IFS7002 with four signal loops is designed to operate with addressable automatic fire detectors and manual call points. It controls addressable executive devices integrated into fire alarm loops. The addressable executive devices can be power supplied from the fire alarm loop or from a power loop. The panel has outputs provided for integration of external executive devices. It is high reliable, multifunctional and versatile device, providing the user with unexpected potential in the design, installation and operation of addressable fire alarm systems.

FEATURES:
- Adjustment of operating modes and parameters of each fire alarm line via built in keypad;
- User oriented menu dialogue for easy and convenient operation;
- LCD for visualization of system checkup and setup modes;
- Touch-panel contributing to the creation of a dynamic keypad;
- LEDs indication for early warning of a break down or extreme conditions;
- Energy independent archive memory saving the event type, date and time, allowing for detailed analysis of the actions of the authorized personnel and of possible problems in the fire protection process of the area;
- User oriented test modes allowing for a total control of the site protected;
- Built-in serial interface for connection to other fire control panels of similar or higher level;
- Built-in serial interface for connection to second level control devices, ability for connection via telephone line and a standard modem;
- System expansion and functional modification (our goal is to constantly improve the fire alarm equipment features), no additional cabling necessary;
- Compatible to random installation design, within the range of the available fire control panels resources.

SPECIFICATIONS:
4 fire alarm loops
1 power loop
2 monitored outputs
1 relay outputs for fire condition
1 programmable relay output for fire condition stage I and/or stage II
1 relay output for fault conditions
Fire alarm zones:
- Maximum number of zone: 500
- Maximum number of fire detectors in a zone: 60
Fire alarm loops:
- Maximum number of fire detectors in a loop: 125
- Connecting line two-wire shielded:
- Maximum consumption of a loop: 200 mA
Power Loop:
- Connecting line: two-wire
- Maximum consumption of the loop: 1A
Monitored outputs: 2 pcs
- Type: potential
- Electrical characteristics: 24±5 V/1A
Relay output for fire condition: 1 pc
- Type: potential free, switching
- Electrical characteristics: 3A/125V AC; 3A/30V DC
Programmable relay output: 1 pc
- Type: potential free, switching
- Electrical characteristics: 3A/125V AC; 3A/30V DC
Relay outputs for fault condition: 1 pc
- Type: potential free, switching
- Electrical characteristics: 3A/125V AC; 3A/30V DC
Indications of registered events:
- Sound signaling: built-in sounder
- Light indication: LED
- Text messages: LCD display,320x240 points, backlit
Power supply:
- Mains: 220/230V; 50Hz
- Back up batteries
Battery type: lead, gel electrolyte
Number of batteries: 2 pcs
Connection: serial connection
Nominal voltage of the back up battery: 2 x 12V
Nominal capacity C20: 18 Ah
Charge voltage: 28.2V
Power supply to external devices
- Voltage: 24±5 V
- Maximum current value: 5A (including current of monitored outputs and power loop)
Dimensions: 493x464x110mm
Weight (batteries not included): 10kg