FS4000/2
 Click to Zoom
Fire control panel with 2 fire lines is designed to operate with conventional automatic fire detectors and manual call points. The panel has outputs provided for external executive devices.

FEATURES:
Fire alarm lines:
- Maximum number of fire detectors in a line: 32
- Connecting line: two-wire
- Maximum resistance of a line: 100 ohm
Current thresholds for:
- Fault condition: 0 - 6 mA
- Duty mode: 6 ~ 16 mA
- Fire condition: 16 ~ 80 mA
- Short circuit: > 80 mA
Monitored outputs for fire condition:
- Number: 2 pcs
- Type : potential, relay with independent control
- Electrical characteristics: 19-27.5 V DC/1 A
Relay outputs for fire condition:
- Number: 2 pcs
- Type : potential-free,1 switching, 1 NO
- Electrical characteristics: 3A/125V AC, 3A/30V DC
Relay output for fault condition:
- Number: 1 pcs
- Type : potential-free, switching
- Electrical characteristics: 3A/125V AC, 3A/30V DC
Relay output for fault condition:
- Number: 1 pcs
- Type: none-monitored type activated on short-circuit (from potential free contact)
- Electrical characteristics: 5 VDC on normal open state
0 VDC in activation mode
Performance:
- Control over fire alarm lines and controllable outputs for fault conditions (short circuit and interruption) and automatic reset.
- Detection of removed fire detector and automatic reset.
- Identification of manual call points.
- LED indication for alarm state and emergency.
- Delay of outputs for fire condition with time period of 1, 2, 3, 4, 5, 6 or 7 minutes after fire condition is registered.
- Option for ''LOGICAL AND '' realization of two fire alarm lines.
- Duty Mode condition with direct activation of Fire Condition 2nd Stage '' for two fire alarm lines.
- Status Indication of the device for data transmission RS485.
- Option for switching on/off interface RS485 communication.
- Built-in sounder for fire condition - one tonal, continuous, can be switched off.
- Built-in sounder for fault condition - one tonal, discontinuous, can be switched off.
- Test mode for fire alarm lines.
- Disabling fire alarm lines.
- Disabling outputs for fire condition.
- Expanding the options by means of extra relay outputs for fire condition for each line and built-in RS485 for operation in a local network.
- Input for remote Reset fires operation;

Indications of registered events:
- Light indication: LED
- Sound: Built-in buzzer
Power supply
- Mains:
Voltage: 100~240 V AC
Frequency: 50/60 Hz
- Backup batteries:
Battery type: lead, gel electrolyte
Number of batteries: 2 pcs
Nominal voltage of the backup battery: 12V
Nominal capacity C20: 4.5 Ah
Charge voltage: 28V DC
Operation in Duty mode upon interruption in main power supply:
24V / 4.5Ah 24V / 1.2Ah
120 h 32h
Consumption on backup batteries supply: 35 mA at 24V DC
Power supply to external devices:
- Voltage: 19~27 V DC
- Maximum current value (including current of contr.outputs) : 1.2A
Fuses
- Main supply: 230V, 4.0 A
- Backup battery: 6.0 A
- Power supply to external devices: 1.85 A automatic
- Monitored outputs: 1.1 A automatic
Dimensions: 313mm x 218mm x 85mm
Weight (backup batteries not included) : 1,5 kg