Conventional line monitoring module is designated to connect conventional fire alarm line (with up to 32 fire detectors) as a part of the addressable fire alarm system IFS7000. The built-in short circuit isolator is available. A heat rate of rise heat detector type FD7120 is integrated into module FD7201. The module is power supplied via the signal loop, and up to 5 modules can be connected in each of the loops. It shall be mounted with base type 7100A. It satisfies the requirements of the European Standard EN54-5, EN54-17 & EN54-18.
Technical data:
Supply voltage: 15~30 VDC
Conventional line voltage: 14~30 VDC
Conventional line current
- Fault condition interruption: 0~2 mA
- Duty mode: 3~3 mA
- Fire condition: 14~50 mA
- Fault condition Short circuit: More than 50 mA
Degree of protection: IP 43
Operation temperature: - 10ºC to 55ºC
Relative humidity: 93±3 % at 40ºC
Dimensions (base included): Ø100, h 47 mm
Casing material: ABS plastics, white
Weight (base included): 0.100 kg